[article]
Titre : |
Cycling losses in refrigeration equipment: An experimental evaluation |
Titre original : |
Pertes lors du cyclage dans les équipements frigorifiques: une évaluation expérimentale |
Type de document : |
texte imprimé |
Auteurs : |
Giacomo Bagarella, Auteur ; Renato M. Lazzarin, Auteur ; Biagio Lamanna, Auteur |
Année de publication : |
2014 |
Article en page(s) : |
pp. 2111–2118 |
Note générale : |
Refrigeration |
Langues : |
Anglais (eng) |
Mots-clés : |
Cycling losses on–off modulation refrigeration thermostatic expansion valve electronic Expansion Valve |
Résumé : |
Cycling losses may be defined as those inefficiencies that reduce the performances of units during the transient period. They may be quantified by comparing the Energy Efficiency Ratio (EER) of a cycling unit and the EER of the same unit working continuously.
The on-off control is the most widespread strategy for modulating; therefore, a reliable evaluation of cycling losses is fundamental to assess the EER of the system. The mentioned losses have been experimentally evaluated on a test rig, and logged data demonstrate a loss up to 13% with respect to steady operations when the load factor is lower than 10% and a Thermostatic Expansion Valve (TEV) is used. The insertion of a solenoid valve in series with the TEV can reduce the losses but the best results are obtained by using the Electronic Expansion Valve (EEV) instead of the TEV. |
En ligne : |
http://www.sciencedirect.com/science/article/pii/S0140700713001989 |
in International journal of refrigeration > Vol. 36 N° 8 (Décembre 2013) . - pp. 2111–2118
[article] Cycling losses in refrigeration equipment: An experimental evaluation = Pertes lors du cyclage dans les équipements frigorifiques: une évaluation expérimentale [texte imprimé] / Giacomo Bagarella, Auteur ; Renato M. Lazzarin, Auteur ; Biagio Lamanna, Auteur . - 2014 . - pp. 2111–2118. Refrigeration Langues : Anglais ( eng) in International journal of refrigeration > Vol. 36 N° 8 (Décembre 2013) . - pp. 2111–2118
Mots-clés : |
Cycling losses on–off modulation refrigeration thermostatic expansion valve electronic Expansion Valve |
Résumé : |
Cycling losses may be defined as those inefficiencies that reduce the performances of units during the transient period. They may be quantified by comparing the Energy Efficiency Ratio (EER) of a cycling unit and the EER of the same unit working continuously.
The on-off control is the most widespread strategy for modulating; therefore, a reliable evaluation of cycling losses is fundamental to assess the EER of the system. The mentioned losses have been experimentally evaluated on a test rig, and logged data demonstrate a loss up to 13% with respect to steady operations when the load factor is lower than 10% and a Thermostatic Expansion Valve (TEV) is used. The insertion of a solenoid valve in series with the TEV can reduce the losses but the best results are obtained by using the Electronic Expansion Valve (EEV) instead of the TEV. |
En ligne : |
http://www.sciencedirect.com/science/article/pii/S0140700713001989 |
|