[article]
Titre : |
Impact of positive-feedback anti-islanding methods on small-signal stability of inverter-based distributed generation |
Type de document : |
texte imprimé |
Auteurs : |
Xiaoyu, Wang, Auteur ; Freitas, W., Auteur |
Année de publication : |
2008 |
Article en page(s) : |
pp. 923 - 931 |
Note générale : |
Energy conversion |
Langues : |
Anglais (eng) |
Mots-clés : |
Distributed power generation feedback invertors grids system stability |
Résumé : |
This paper investigates the impact of positive-feedback anti-islanding methods on the small-signal stability of grid-connected inverter-based distributed generation. The maximum power transfer capability of a distributed generator (DG) is analyzed. Sensitivity studies are conducted for DGs equipped with the Sandia frequency shift anti-islanding scheme. Factors such as positive-feedback gain, initial chopping fraction, local load level, and network line impedance are investigated. The maximum power transfer limit versus positive-feedback gain curve is proposed as an index for the stability analysis. The results show that the positive-feedback anti-islanding scheme does have the potential to destabilize the grid-connected DG system when the grid is weak or the DG size is large. A curve that relates the maximum stable DG power transfer level versus the islanding detection time is proposed to quantify the destabilizing effect of the positive-feedback-based anti-islanding schemes. |
En ligne : |
http://ieeexplore.ieee.org/xpl/articleDetails.jsp?arnumber=4567146&sortType%3Das [...] |
in IEEE transactions on energy conversion > Vol. 23 n°3 (Septembre 2008) . - pp. 923 - 931
[article] Impact of positive-feedback anti-islanding methods on small-signal stability of inverter-based distributed generation [texte imprimé] / Xiaoyu, Wang, Auteur ; Freitas, W., Auteur . - 2008 . - pp. 923 - 931. Energy conversion Langues : Anglais ( eng) in IEEE transactions on energy conversion > Vol. 23 n°3 (Septembre 2008) . - pp. 923 - 931
Mots-clés : |
Distributed power generation feedback invertors grids system stability |
Résumé : |
This paper investigates the impact of positive-feedback anti-islanding methods on the small-signal stability of grid-connected inverter-based distributed generation. The maximum power transfer capability of a distributed generator (DG) is analyzed. Sensitivity studies are conducted for DGs equipped with the Sandia frequency shift anti-islanding scheme. Factors such as positive-feedback gain, initial chopping fraction, local load level, and network line impedance are investigated. The maximum power transfer limit versus positive-feedback gain curve is proposed as an index for the stability analysis. The results show that the positive-feedback anti-islanding scheme does have the potential to destabilize the grid-connected DG system when the grid is weak or the DG size is large. A curve that relates the maximum stable DG power transfer level versus the islanding detection time is proposed to quantify the destabilizing effect of the positive-feedback-based anti-islanding schemes. |
En ligne : |
http://ieeexplore.ieee.org/xpl/articleDetails.jsp?arnumber=4567146&sortType%3Das [...] |
|